10.24.37 Temperature reading — Weighting of internal measurement (0 to 100%)
Options:
Setting option between 0 - 100
Specifying the weighting of the internal measurement from 0 to 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement" or "Internal
and 2x external measurement".
10.24.38 Temperature reading — Weighting of external measurement (0 to 100%)
Options:
Setting option between 0 - 100
Specifying the weighting of the external measurement from 0 to 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement", "2x external
measurement" or "Internal and 2x external measurement".
10.24.39 Temperature reading — Weighting of external measurement 2 (0 to 100%)
Options:
Setting option between 0 - 100
Specifying the weighting of the external measurement 2 from 0 to 100%. The setting together
with the weighting of the external measurement (0 - 100%) must result in 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "2x external measurement" or "Internal and 2x
external measurement".
10.24.40 Temperature reading — Cyclic sending of the actual temperature (min)
Options:
Setting option between 5 - 240
The current actual temperature used by the device can be cyclically transmitted to the bus.