KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
│
221
10.24.26 Setpoint settings — Set-point temperature for frost protection (°C)
Options:
Setting option between 5 - 15
Function for protecting the building against the cold. On devices with a display, this mode is
indicated by the frost protection icon. Manual operation is blocked.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
10.24.27 Setpoint settings — Send current setpoint
Options:
Cyclic and during change
Only for change
The current setpoint value can be sent to the bus either cyclically and after a change, or only
after a change.
10.24.28 Setpoint settings — Cyclic sending of the current set-point temperature (min)
Options:
Setting option between 5 - 240
This parameter is used to specify the amount of time that will elapse before the current setpoint
value is automatically transmitted.
Note
This parameter is only available when the "Send current setpoint" is set on "Only
during change".
10.24.29 Setpoint adjustment — Maximum manual increase during heating mode (0 - 9°C)
Options:
Setting option between 0 - 9
This preset can be used to limit the manual increase during heating.
Note
This parameter is only available when parameter "Controller function" is set
on "Heating" and parameter "Control value type" on "2-point 1 bit, On/Off" or
"2-point 1 byte, 0/100%".