• Configure the DeviceNet Scanner. Add the drive to Scanlist and
edit I/O parameters. Select Polled or Change of State/Cyclic.
Then enter the input and output sizes of the I/O assemblies that
will be used (e.g. for Basic Speed Control Assemblies 20 and
70, each size is set to 4 bytes).
• For convenience, you can also edit the Input and Output
memory mappings. By default the two 16-bit input words are
mapped into a single 32-bit double word. It is more convenient,
however, to map them into separate double words. Output
words can be mapped similarly.