Technical data
86
Current consumption:
• 250 mA max. (5 V), supplied by the RMIO board
• 15 mA max. (24 V) from the network supply.
General:
• Estimated min. lifetime: 100 000 h
• All materials are UL/CSA approved
• Complies with EMC Standards EN 50081-2 and EN 50082-2
Fieldbus link
Compatible Devices:
Any ODVA-compliant DeviceNet scanner
supporting Poll - Response commands to Group 2 only Slaves
Medium:
•
Termination:
121 ohm, 1%, Metal Film, 1/4 W
•
DeviceNet Cables:
YR-29790 (Thick DeviceNet Cable)
YR-29832 (Thin DeviceNet Cable)
•
Maximum Bus Length:
1200 m
Topology:
Multi-drop
Serial Communication Type:
Asynchronous, half Duplex
Transfer Rate:
125, 250 or 500 kbit/s
Protocol:
DeviceNet
Summary of Contents for RDNA-01
Page 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 52: ...Communication profiles 52 ...
Page 80: ...Diagnostics 80 ...
Page 84: ...Definitions and abbreviations 84 ...
Page 87: ......