Drive configuration
42
08 Output I/O Par 1
Defines the data word or drive parameter that can be
written
with
Assembly object instances 102 and 121 (see sections
User
Specific assembly
and
EXTENDED SPEED CONTROL PLUS
DRIVE PARAMETERS assembly
in chapter
Communication
).
The content is defined by a decimal number in the range of 0 to
32767 as follows:
The parameter area is allocated as follows:
Parameter number with format xxyy, where xx is the parameter
group number (0 to 99) and yy is the parameter number index
inside the group (01 to 99).
Note:
Group 0 is a virtual group for the data sets.
0
not used
1 - 99
data set area of the drive
101 - 9999
parameter area of the drive
10000 - 32767
not supported by the drive
The data set area is allocated as follows:
1
data set 1 word 1
2
data set 1 word 2
3
data set 1 word 3
4
data set 2 word 1
5
data set 2 word 2
6
data set 2 word 3
7
data set 3 word 1
…
99
data set 33 word 3
Summary of Contents for RDNA-01
Page 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 52: ...Communication profiles 52 ...
Page 80: ...Diagnostics 80 ...
Page 84: ...Definitions and abbreviations 84 ...
Page 87: ......