Communication
63
Product Code
Every ABB drive type or application of the drive has a dedicated
product code.
Revision
Revision attribute, which consists of Major and Minor Revisions,
identifies the Revision of the item the Identity Object is
representing.
Status
This attribute represents the current status of the entire device. Its
value changes as the state of the device changes. The Status
attribute is a WORD, with the following bit definitions:
Bit(s)
Type/Name
Definition
0 Owned
TRUE
indicates
the
device (or an object within
the device) has an owner. Within the
Master/Slave paradigm the setting of this bit
means that the Predefined Master/Slave
Connection Set has been allocated to a master.
Outside the Master/Slave paradigm the
meaning of this bit is to be defined.
1
Reserved, set to 0.
2
Configured
TRUE indicates the application of the device
has been configured to do something that
differs from the “out–of–box” default. This does
not include configuration of the
communications.
3
Reserved, set to 0.
4,5,6,7 Vendor–specific
8
Minor Recoverable
Fault
TRUE indicates the device detected a
recoverable problem. The problem does not
cause the device to go into a faulted state.
9
Minor
Unrecoverable Fault
TRUE indicates the device detected a
unrecoverable problem. The problem does not
cause the device to go into a faulted state.
10
Major Recoverable
Fault
TRUE indicates the device detected a problem
which caused the device to go into the “Major
Recoverable Fault” state.
Summary of Contents for RDNA-01
Page 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 52: ...Communication profiles 52 ...
Page 80: ...Diagnostics 80 ...
Page 84: ...Definitions and abbreviations 84 ...
Page 87: ......