Quick start-up guide
27
ODVA Extended Speed Control plus Drive Parameters assemblies on
ACS800
Drive Parameter
Example setting for ACS800
10.01 EXT1 STRT/STP/DIR
COMM.CW
10.03 REF DIRECTION
REQUEST
11.03 EXT REF1 SELECT
COMM. REF
16.01 RUN ENABLE
YES
16.04 FAULT RESET SEL
COMM.CW
51.01 MODULE TYPE
DEVICENET
51.02 Module MacID
2
51.03 Module baud rate
2 (500 kbit/s)
51.04 HW/SW option
1 (use software settings)
51.05 Stop function
0 (ramp stop)
51.06 Output instance
121 (ODVA Extended Speed plus Drive
Parameters Assembly) Command word
and Reference 1 are according to ODVA.
51.07 Input instance
171 (ODVA Extended Speed plus Drive
Parameters Assembly) Status word and
Actual 1 are according to ODVA.
51.08 Output I/O par 1
2202 (22.02 ACCEL TIME 1)
51.09 Output I/O par 2
2202 (22.03 DECEL TIME 1
51.10 Output I/O par 3
1202 (12.02 CONST SPEED 1)
51.11 Output I/O par 4
1203 (12.03 CONST SPEED 2)
51.12 Input I/O par 1
104 (01.04 CURRENT)
51.13 Input I/O par 2
106 (01.06 POWER)
51.14 Input I/O par 3
117 (01.17 DI6-1 STATUS)
51.15 Input I/O par 4
118 (01.18 AI1)