Communication
71
Acknowledge Handler Object, Class 0x2B
The Acknowledge Handler Object is used to manage the reception
of message acknowledgements. This object communicates with a
message producing Application Object within the device. The
Acknowledge Handler Object notifies the producing application of
acknowledge reception, acknowledge timeouts and production
retry limit.
7 Produced
Connection
Size
Get
Maximum number of bytes
transmitted across this
Connection
0,0,N/A
UINT16
8 Consumed
Connection
size
Get
Maximum number of bytes
received across this Connection
0,0,N/A
UINT16
9 Expected
Packet Rate
Get,Set
Defines timing associated with
this Connection.
0,0,0xffff
UINT16
12 Watchdog
Timeout Action
Get
Defines how to handle
Inactivity/Watchdog timeouts.
N/A,N/A,
N/A
UINT8
13 Produced
Connection
Path Length
Get
Number of bytes in the
produced_connection_path
length attribute
3,0,3
UINT16
14 Produced
Connection
Path
Get
Application Object producing
data on this Connection
0x62
0x39
0x37,
0,N/A
Array of
UINT8
15 Consumed
Connection
Path Length
Get
Number of bytes in the
consumed_connection_path
length attribute
5,0,5
UINT16
16 Consumed
Connection
Path
Get
Specifies the Application
Object(s) that are to receive the
data consumed by this
Connection Object.
0x62
0x31
0x35,
N/A,N/A
Array of
UINT8
17 Production
Inhibit Time
Get,Set
Defines minimum time between
new data production.
0,3FFF,
N/A
UINT16
# Attribute
name
Services Description
Default,
Minimum,
Maximum
Data
type
Summary of Contents for RDNA-01
Page 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 52: ...Communication profiles 52 ...
Page 80: ...Diagnostics 80 ...
Page 84: ...Definitions and abbreviations 84 ...
Page 87: ......