Diagnostics
79
Installation problems
Verify all the connections on the module:
• Check that the DeviceNet cables are connected to terminal
block X1 as described in chapter
Electrical installation
.
• Check that an external voltage of 24 V DC is applied to
terminals X1:1 and X1:5.
• Check that the RDNA-01 module is properly inserted into the
option slot.
• Check the fastening of the RDNA-01 module with the 2 screws.
Drive setup
The fieldbus parameter group is not shown on the panel:
• Enable the RDNA-01 by setting the appropriate drive
parameter.
The RDNA-01 is using default values:
• Verify that the fieldbus parameter group is set up correctly. If so,
turn off and on the power to the drive or issue a ‘Fieldbus
Adapter parameter refresh’ command. This will make the
module re-read its setup parameters.
Drive actual values can be read, but the control commands (start/
stop or reference) do not go through:
• Check that the control location parameters of the drive are set to
use the RDNA-01 as the source of the required command.
• Check that the drive is in REMOTE control.
PLC programming
The PLC program is beyond ABB Drives support. Contact the
manufacturer for assistance.
Scanner fault indications
Refer to scanner documentation.
Summary of Contents for RDNA-01
Page 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 52: ...Communication profiles 52 ...
Page 80: ...Diagnostics 80 ...
Page 84: ...Definitions and abbreviations 84 ...
Page 87: ......