Drive configuration
43
09 to 11 Output I/O Par 2 to Output I/O Par 4
See parameter
08 Output I/O Par 1
.
12 Input I/O Par 1
Defines a data word or drive parameter that can be
read
with
Assembly object instances 103 and 171 (see sections
User
Specific assembly
and
EXTENDED SPEED CONTROL PLUS
DRIVE PARAMETERS assembly
in chapter
Communication
).
The content is defined by a decimal number in the range of 0 to
32767 as follows:
The parameter area is allocated as follows:
Parameter number with format xxyy, where xx is the parameter
group number (1 to 99) and yy is the parameter number index
inside the group (01 to 99).
0
not used
1 - 99
data set area of the drive
101 - 9999
parameter area of the drive
10000 - 32767
not supported by the drive
The data set area is allocated as follows:
1
data set 1 word 1
2
data set 1 word 2
3
data set 1 word 3
4
data set 2 word 1
5
data set 2 word 2
6
data set 2 word 3
7
data set 3 word 1
…
99
data set 33 word 3