Quick start-up guide
24
Note:
The new settings take effect only when the module is
powered up the next time or when a ‘Fieldbus Adapter parameter
refresh’ is given (see the drive documentation).
Example Configurations
ODVA Basic Speed Control on ACS800
Drive Parameter
Example setting for ACS800
10.01 EXT1 STRT/STP/DIR
COMM.CW
10.03 REF DIRECTION
REQUEST
11.03 EXT REF1 SELECT
COMM. REF
16.01 RUN ENABLE
YES
16.04 FAULT RESET SEL
COMM.CW
51.01 MODULE TYPE
DEVICENET (Verify only)
51.02 Module MacID
2
51.03 Module baud rate
2 (500 kbit/s)
51.04 HW/SW option
1 (use software settings)
51.05 Stop function
0 (ramp stop)
51.06 Output instance
20 (ODVA Basic Speed Control)
51.07 Input instance
70 (ODVA Basic Speed Control)
98.02 COMM MODULE LINK
FIELDBUS
98.07 COMM PROFILE
GENERIC