Drive configuration
41
The following table shows the possible combinations of output and
input instances.
Note:
Using instance 103 in Generic drive profile with ODVA output
instances (20, 21, 121) is allowed but not recommended.
Selecting an invalid combination will reset the module and
automatically configure the instances as follows:
1) If the output instance is invalid, instance
20
will be selected.
2) If the output instance is valid, but the input instance is invalid,
the default input instance will be selected as follows:
Possible instance combinations
Output instance
Input instance
Communication
profile to be used
20
70
Generic Drive profile
71
Generic Drive profile
171
Generic Drive profile
21
70
Generic Drive profile
71
Generic Drive profile
171
Generic Drive profile
121
70
Generic Drive profile
71
Generic Drive profile
171
Generic Drive profile
100
101
ABB Drives profile
103
ABB Drives profile
102
101
ABB Drives profile
103
ABB Drives profile
Output instance
Default input instance
20
70
21
71
100
101
102
103
121
171