56 Start-up
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
The table below gives the recommended drive parameter settings.
Output data
Modbus
register
Input data
Modbus
register
Control word
(4)00001
Status word
(4)00051
Speed reference
(4)00002
Speed actual value
(4)00052
Reference 2
(Not used)
(4)00003
Actual value 2
(Not used)
(4)00053
Constant speed 1
1)
(4)00004
(4)00005
Power
1)
(4)00054
(4)00055
Constant speed 2
1)
(4)00006
(4)00007
DC bus voltage
1)
(4)00056
(4)00057
1)
Example
Drive parameter
Setting for ACS880
drives
Description
50.01 FBA A enable
1
= Enable
Enables communication between
the drive and the fieldbus adapter
module.
50.02 FBA A comm loss
func
1
= Fault
2)
Enables fieldbus A
communication fault monitoring.
50.03 FBA A comm loss t
out
3.0 s
2)
Defines the fieldbus A
communication break supervision
time.
50.04 FBA A ref1 type
4
= Speed
Selects the fieldbus A reference 1
type and scaling.
51.01 FBA type
485
= RS-485
1)
Displays the type of the fieldbus
adapter module.
51.02 Profile
1
= ABB Enhanced
2)
Selects the ABB Drives -
Enhanced profile.
51.03 Station ID
3
2)
Defines the address of the
device.
51.04 Baud rate
4
= 115.2 kbit/s
2)
Selects the baud rate of the link.
Note:
The baud rate of the
master has to be the same.
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...