66 Communication profiles
References
References are 16-bit words containing a sign bit and a 15-bit
integer. A negative reference (indicating reversed direction of
rotation) is formed by calculating the two’s complement from the
corresponding positive reference.
ABB drives can receive control information from multiple sources
including analog and digital inputs, the drive control panel and a
communication module (for example, FSCA-01). To have the drive
controlled through the fieldbus, the module must be defined as the
source for control information, for example, reference.
Scaling
References are scaled as shown below.
Note:
The values of REF1 MAX and REF2 MAX are set with drive
parameters. See the drive manuals for further information.
In ACSM1, ACS850, ACQ810, ACS880, ACS860 and ACS530 the
speed reference (REFx) in decimal (0…20000) corresponds to
0…100% of the speed scaling value (as defined with a drive
parameter, eg, ACS880 parameter 46.01 Speed scaling).
In ACS355, drive parameter REFx MIN may limit the actual
minimum reference.
Drive
Fieldbus
0
REFx MAX / Speed scale
-(REFx MAX) / Speed scale
0
REF2: -10000
REF1: -20000
REF2: 10000
REF1: 20000
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...