42 Start-up
FSCA-01 configuration parameters – group B (group 2)
Note:
The actual parameter group number depends on the drive
type. Group B (group 2) corresponds to:
•
parameter group
55
in ACS355
•
parameter group
53
in ACSM1, ACS530, ACS850 and
ACQ810
•
parameter group
53
in ACS880 if the adapter is installed as
fieldbus adapter A or group
56
if the adapter is installed as
fieldbus adapter B
No.
1)
Name/Value
Description
Default
01
FBA data out1
(master to drive)
Selects the drive parameter address into
which the value of the DATA OUT 1 register is
written (from the master to the server). The
Modbus register address maps are explained
in chapter
Communication protocol
.
The content is defined by a decimal number in
the range of 0 to 9999 as follows:
0
= None
0
= None
Not used
101…9999
Parameter index with format
xxyy
, where
•
xx
is the parameter group number (
1
…
99
)
•
yy
is the parameter number index within
that group (
01
…
99
).
Other
Path to parameter area selection.
02…
12
FBA data out2…
FBA data out12
See parameter
01
FBA data out1
.
0
= None
1)
The number of parameters in this group may vary by drive type and drive firmware.
0
Not used
1…99 Virtual address area of drive control.
Not used with Modbus/RTU.
101…
9999
Parameter area of the drive
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...