Start-up 47
5102 FB PAR 2
(PROFILE)
1
(= ABB
Enhanced)
Selects the ABB Drives -
Enhanced profile.
5103 FB PAR 3
(STATION ID)
3
2)
Defines the address of the device.
5104 FB PAR 4
(BAUD RATE)
4
(= 115.2 kbit/s)
2)
Selects the baud rate of the link.
Note:
The baud rate of the master
has to be the same.
5105 FB PAR 5
(PARITY)
0
(= 8 None 1)
2)
Defines the use of parity and stop
bit(s) and the data length.
Note:
The parity setting of the
master has to be the same.
5106 FB PAR 6
(MODBUS TIMEOUT)
10
2)
Sets the communication timeout
as 1 second.
5107 FB PAR 7
(TIMEOUT MODE)
2
(=Ctrl write)
2)
The timeout feature monitors the
updating of the Control word and
Reference 1.
3018 COMM FAULT FUNC
1
= FAULT
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT TIME
3.0 s
2)
Defines the fieldbus
communication break supervision
time.
5401 FBA DATA IN 1
106
2)
Power
5402 FBA DATA IN 2
107
2)
DC bus voltage
5501 FBA DATA OUT 1
1202
2)
Constant speed 1
5502 FBA DATA OUT 2
1203
2)
Constant speed 2
5127 FBA PAR REFRESH
1
= REFRESH
Validates the FSCA-01
configuration parameter settings.
9904 MOTOR CTRL
MODE
2
= VECTOR:
TORQ
Selects the vector control mode as
the motor control mode.
1001 EXT1 COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1002 EXT2 COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
Drive parameter
Setting for
ACS355 drives
Description
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...