40 Start-up
28
Par table ver
Read-only.
Displays the parameter table
revision of the fieldbus adapter module
mapping file stored in the memory of the
drive.
In format
xyz
, where
x
= major revision number
y
= minor revision number
z
= correction number
OR
in format
axyz
, where
a
= major revision number
xy
= minor revision number
z
= correction number or letter.
N/A
Parameter table revision
29
Drive type code
Read-only.
Displays the drive type code of
the fieldbus adapter module mapping file
stored in the memory of the drive.
N/A
Drive type code of the fieldbus adapter
module mapping file
30
Mapping file ver
Read-only.
Displays the fieldbus adapter
module mapping file revision stored in the
memory of the drive in decimal format.
N/A
Mapping file revision
31
D2FBA comm sta
Read-only.
Displays the status of the
fieldbus adapter module communication.
Note:
The value names may vary by drive.
0
= Idle
OR
4
= Off-line
0
= Idle
Adapter is not configured.
1
= Exec.init
Adapter is initializing.
2
= Time out
A timeout has occurred in the
communication between the adapter and
the drive.
3
= Conf.err
Adapter configuration error: The major or
minor revision code of the common
program revision in the fieldbus adapter
module is not the revision required by the
module or mapping file upload has failed
more than three times.
4
= Off-line
Adapter is off-line.
5
= On-line
Adapter is on-line.
6
= Reset
Adapter is performing a hardware reset.
No.
Name/Value
Description
Default
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...