Start-up 57
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal)
→
READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal)
→
OPERATING (Speed mode).
51.05 Parity
0
= 8 None 1
2)
Defines the use of parity and stop
bit(s) and the data length.
Note:
The parity setting of the
master has to be the same.
51.06 Modbus timeout
10
2)
Sets the communication timeout
as 1 second.
51.07 Timeout mode
1
=
Any message
2)
Timeout counter is reset when
any Modbus register of the drive
is accessed.
52.01 FBA data in1
01.14
2)
Output power
52.03 FBA data in3
01.11
2)
DC voltage
53.01 FBA data out1
22.26
2)
Constant speed 1
53.03 FBA data out3
22.27
2)
Constant speed 2
51.27 FBA par refresh
1
= Configure
Validates the FSCA-01
configuration parameter settings.
20.01 Ext1 commands
12
= Fieldbus A
Selects the fieldbus A interface
as the source of the start and
stop commands for external
control location 1.
20.02 Ext1 start trigger
1
= Level
2)
Defines the start signal for
external control location 1 as
level-triggered.
22.11 Speed ref1
selection
4
= FB A ref1
Selects the fieldbus A reference 1
as the source for speed
reference 1.
1) Read-only or automatically detected/set
2) Example
Drive parameter
Setting for ACS880
drives
Description
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...