Start-up 45
Starting up ACS355 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter
9802 COMM PROT SEL
to EXT
FBA.
3. Set the FSCA-01 configuration parameters in group
51
.
•
Select the communication protocol with parameter
5125
and profile with parameter
5102
.
•
Configure the network settings with parameters
5103
…
5105
.
•
With parameters
5106
and
5107
, select how the adapter
module detects fieldbus communication breaks.
4. With parameter
3018 COMM FAULT FUNC
, select how the
drive reacts to a fieldbus communication break.
5. With parameter
3019 COMM FAULT TIME
, define the time
between communication break detection and the selected
action.
6. Define the process data transferred to and from the drive in the
FSCA-01 configuration parameter groups
54
and
55
.
Note:
The adapter module assigns the Control word, Status
word, references 1…2 and actual values 1…2 automatically to
Modbus registers. Process data groups are not available for
the ABB Drives - Classic communication profile.
7. Validate the settings made in parameter groups
51
,
54
and
55
by setting parameter
5127 FBA PAR REFRESH
to REFRESH.
8. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...