62 Communication profiles
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION ENABLED
.
Note:
Run enable signal must be active;
see drive documentation. If the drive is set
to receive the Run enable signal from the
fieldbus, this bit activates the signal.
0
Inhibit operation. Proceed to
OPERATION
INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RAMP
FUNCTION GENERATOR: OUTPUT
ENABLED
.
0
Force Ramp Function Generator output to
zero. Drive ramps to stop (current and DC
voltage limits in force).
5
RAMP_HOLD
1
Enable ramp function.
Proceed to
RAMP FUNCTION
GENERATOR: ACCELERATOR
ENABLED
.
0
Halt ramping (Ramp Function Generator
output held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATION
.
Note:
This bit is effective only if the
fieldbus interface is set as the source for
this signal by drive parameters.
0
Force Ramp Function Generator input to
zero.
7
RESET
0 –> 1 Fault reset if an active fault exists.
Proceed to
SWITCH-ON INHIBITED
.
Note:
This bit is effective only if the
fieldbus interface is set as the source for
this signal by drive parameters.
0
Continue normal operation.
8…9 Reserved.
Bit
Name
Value
STATE/Description
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...