Start-up 55
Note 2:
With 32-bit parameters, one can only assign process
data to every second configuration parameter (eg,
52.01
,
52.03
,
52.05
, and so on).
8. Save the valid parameter values to permanent memory by
setting parameter
96.07 Parameter
save
to Save.
9. Validate the settings made in parameter groups
51
,
52
and
53
by setting parameter
51.27 FBA par refresh
to Configure.
10. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Parameter setting examples – ACS880
Speed control using the ABB Drives - Enhanced
communication profile
This example shows how to configure a speed control application
that uses the ABB Drives - Enhanced profile.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see the state machine on
page
65
.
When Reference 1 (REF1) is used, a reference value of ±20000
(4E20h) corresponds to the reference set with parameter
46.01
Speed scaling
in the forward and reverse directions.
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...