52 Start-up
51.05 FBA PAR5
(PARITY)
0
(= 8 None 1)
2)
Defines the use of parity and
stop bit(s) and the data length.
Note:
The parity setting of the
master has to be the same.
51.06 FBA PAR6
(MODBUS TIMEOUT)
10
2)
Sets the communication timeout
as 1 second.
51.07 FBA PAR7
(TIMEOUT MODE)
2
(=Ctrl write)
2)
The timeout feature monitors the
updating of the Control word and
Reference 1.
52.01 FBA DATA IN1
122
2)
Power
52.03 FBA DATA IN3
107
2)
DC bus voltage
53.01 FBA DATA OUT1
2408
2)
Constant speed
53.03 FBA DATA OUT3
2410
2)
Speed reference for jogging
function 1
51.27 FBA PAR REFRESH
REFRESH
Validates the FSCA-01
configuration parameter settings.
10.01 EXT1 START FUNC
FBA
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
10.04 EXT2 START FUNC
FBA
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
24.01 SPEED REF1 SEL
FBA REF1
Selects the fieldbus reference 1
as the source for speed
reference 1.
32.01 TORQ REF1 SEL
FBA REF2
Selects the fieldbus reference 2
as the source for torque
reference 1.
34.01 EXT1/EXT2 SEL
P.FBA MAIN CW.15
Enables external control location
1/2 selection through the fieldbus
only (bit 15 in the fieldbus
Control word).
34.03 EXT1 CTRL MODE1
Speed
Selects speed control as the
control mode 1 for external
control location 1.
Drive parameter
Setting for ACSM1
drives
Description
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...