48 Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal)
→
READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal)
→
OPERATING (Speed mode)
or
C7Fh (3199 decimal)
→
OPERATING (Torque mode).
1102 EXT1/EXT2 SEL
8
= COMM
Enables external control location
1/2 selection through the fieldbus.
1103 REF1 SELECT
8
= COMM
Selects the fieldbus reference 1 as
the source for speed reference.
1106 REF2 SELECT
8
= COMM
Selects the fieldbus reference 2 as
the source for torque reference.
1601 RUN ENABLE
7
= COMM
Selects the fieldbus interface as
the source for the inverted Run
enable signal (Run disable).
1604 FAULT RESET SEL
8
= COMM
Selects the fieldbus interface as
the source for the fault reset
signal.
1) Read-only or automatically detected/set
2) Example
Drive parameter
Setting for
ACS355 drives
Description