86 Diagnostics
(4)00094
Last register that was written successfully
(4)00095
Last register that was read successfully
Error code
Description
Situation
0x00
No error
Used when a Modbus query was
successful
0x02
Low or high limit
exceeded
Change access with a value
outside the value limits
0x03
Faulty subindex
Access to an unavailable
subindex of an array parameter
0x05
Incorrect data type
Change access with a value that
does not match the data type of
the parameter
0x65
General error in drive
communication
Undefined error when handling a
Modbus query
0x66
Timeout
Timeout in drive communication
when handling a Modbus query
0x70
Read-only
An attempt to write a non-zero
value to a read-only drive
parameter
0x71
Parameter group
ended
An attempt to write to multiple
parameter groups
0x72
MSB is not zero
An attempt to write a 16-bit
parameter with a 32-register
address and the MSB bytes are
not zero
0x73
LSB query start
An attempt to access only the
LSB register of the 32-bit
parameter
0x74
MSB query end
An attempt to access only the
MSB register of the 32-bit
parameter
Address
Registers (16-bit word)
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...