64 Communication profiles
7
ALARM
1
Warning/Alarm
0
No warning/alarm
8
AT_
SETPOINT
1
OPERATION.
Actual value equals reference
(= is within tolerance limits, ie, in speed
control, speed error is 10% max. of nominal
motor speed).
0
Actual value differs from reference (= is
outside tolerance limits.)
9
REMOTE
1
Drive control location: REMOTE (EXT1 or
EXT2)
0
Drive control location: LOCAL
10
ABOVE_
LIMIT
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter).
Valid in both directions of rotation.
0
Actual frequency or speed within supervision
limit
11
EXT_CTRL_
LOC
1
External Control Location EXT2 selected.
Note concerning ACS880 and ACS860:
This bit is effective only if the fieldbus
interface is set as the target for this signal by
drive parameters. User bit 0 selection
(06.33).
0
External Control Location EXT1 selected
12
EXT_RUN_
ENABLE
1
External Run Enable signal received.
Note concerning ACS880 and ACS860:
This bit is effective only if the fieldbus
interface is set as the target for this signal by
drive parameters. User bit 1 selection
(06.34).
0
No External Run Enable signal received
13…
14
Drive-specific (For information, see the drive documentation.)
15
FBA_ERROR
1
Communication error detected by fieldbus
adapter module
0
Fieldbus adapter communication OK
Bit
Name
Value
STATE/Description
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...