84 Diagnostics
LED indications
The adapter module is equipped with three bicolor diagnostic
LEDs. The LEDs are described below.
Name
Color
Function/state
HOST
Flashing green
Establishing communication to host
Green
Connection to host OK
Flashing red
Communication to host lost temporarily
Orange
Configuration error
Flashing orange,
alternating with
the MODULE
flashing orange
Internal file system error. The error may
be cleared by cycling drive power. If the
error persists, contact your local ABB
representative.
MODULE
Green
The device is operating in a normal
condition.
Off
Communication to host lost temporarily
(or no power applied to the device)
Flashing red
Start-up initialization
Orange
Configuration error
Flashing orange,
alternating with
the HOST
flashing orange
Internal file system error. The error may
be cleared by cycling drive power. If the
error persists, contact your local ABB
representative.