70 Communication protocol
Register addressing
The address field of Modbus requests for accessing holding
registers is 16 bits. This allows the Modbus protocol to support
addressing of 65536 holding registers.
Historically, Modbus master devices used 5-digit decimal
addresses from 40001 to 49999 to represent holding register
addresses. 5-digit decimal addressing limited to 9999 the number
of holding registers that could be addressed.
Modern Modbus master devices typically provide a means to
access the full range of 65536 Modbus holding registers. One of
these methods is to use 6-digit decimal addresses from 400001 to
465536. This manual uses 6-digit decimal addressing to represent
Modbus holding register addresses.
Modbus master devices that are limited to 5-digit decimal
addressing may still access registers 400001 to 409999 by using
5-digit decimal addresses 40001 to 49999. Registers 410000-
465536 are inaccessible to these masters.
Note:
Register addresses of the 32-bit parameters cannot be
accessed by using 5-digit register numbers.
Function codes
The adapter module supports the Modbus function codes shown
below.
Function
code
Name
Description
03h
Read Holding Registers Reads the contents of a
contiguous block of holding
registers in a server device.
06h
Write Single Register
Writes a single holding register in
a server device.
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...