Communication profiles 63
Status word contents
The table below shows the contents of the Status word for the ABB
Drives communication profile. The upper case boldface text refers
to the states shown in the state machine on page
65
.
10
REMOTE_
CMD
1
Fieldbus control enabled.
0
Control word and reference not getting
through to the drive, except for CW bits
OFF1, OFF2 and OFF3.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2.
Effective if control location parameterized
to be selected from fieldbus.
0
Select External Control Location EXT1.
Effective if control location parameterized
to be selected from fieldbus.
12…
15
Drive-specific (For information, see the drive documentation.)
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
RDY_RUN
1
READY TO OPERATE
0
OFF1 ACTIVE
2
RDY_REF
1
OPERATION ENABLED
0
OPERATION INHIBITED
3
TRIPPED
1
FAULT
0
No fault
4
OFF_2_STA
1
OFF2 inactive
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 inactive
0
OFF3 ACTIVE
6
SWC_ON_
INHIB
1
SWITCH-ON INHIBITED
0
–
Bit
Name
Value
STATE/Description
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...