![background image](http://html.mh-extra.com/html/abb/fsca-01/fsca-01_user-manual_200076.webp)
76 Communication protocol
ABB Drives profile - Enhanced
The ABB Drives profile - Enhanced communication profile provides
register mapped access to the control, status, reference and actual
values of the ABB Drives profile. The mapping of the registers has
been enhanced to allow writing of control and reading of status in a
single Read/Write Multiple Register request.
Note:
If 32-bit parameters are mapped to DATA IN or DATA OUT,
adjust the length of the request message to fit both words of the
parameter.
Register Address
1), 2)
Register Data (16-bit)
(4)00001
ABB Drives Profile Control
(4)00002
ABB Drives Profile Reference 1
(4)00003
ABB Drives Profile Reference 2
(4)00004
DATA OUT 1
(4)00005
DATA OUT 2
(4)00006
DATA OUT 3
(4)00007
DATA OUT 4
(4)00008
DATA OUT 5
(4)00009
DATA OUT 6
(4)00010
DATA OUT 7
(4)00011
DATA OUT 8
(4)00012
DATA OUT 9
(4)00013
DATA OUT 10
(4)00014
DATA OUT 11
(4)00015
DATA OUT 12
(4)00051
ABB Drives Profile Status
(4)00052
ABB Drive Profile Actual 1
(4)00053
ABB Drive Profile Actual 2
(4)00054
DATA IN 1
(4)00055
DATA IN 2
(4)00056
DATA IN 3
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...