Communication protocol 75
(4)20000…(4)29999
Drive Parameter Access (32-bit)
(not supported with ACS355)
Register Address = (4)20000 + 200 × Group +
2 × Index
Example for Drive Parameter 1.27:
(4)20000 + 200 × 1 + 2 × 27 = (4)20254
Note
: Addressing depends on the address
mode selected with parameter
12
in group A
(51/151, 54/154).
Register Address
1), 2)
Register Data (16-bit)
1)
6-digit register addressing ([4]00001) is used instead of 5-digit register
addressing ([4]0001) to describe register map. See section
Register
addressing
on page
70
for additional information.
2)
Register addresses of the 32-bit parameters cannot be accessed by
using 5-digit register numbers.
Summary of Contents for FSCA-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Page 4: ......
Page 8: ...8 Table of contents ...
Page 18: ...18 About the manual ...
Page 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 68: ...68 Communication profiles ...
Page 82: ...82 Communication protocol ...