1-226
ACH550-UH User’s Manual
Embedded fieldbus
86
OK.ALARM
Indicates the current alarm state of the drive
(1 = ALARM, 0 = OK).
87
OK.MAINT
Indicates the current maintenance state of the drive
(1 = MAINT, 0 = OK).
Maintenance triggers are configured in drive parameter
Group 29.
88
ALARM WORD1
This point is a bit-field indicating active alarms in the drive.
0308
89
ALARM WORD2
This point is a bit-field indicating active alarms in the drive.
0309
90
LAST FAULT
This point is first in the drive's fault log and indicates the most
recent fault declared.
0401
91
PREV FAULT 1
This point is second in the drive's fault log and indicates the
previous fault declared.
0412
92
PREV FAULT 2
This point is last in the drive's fault log and indicates the
oldest fault in the log.
0413
93
OK.FAULT
Indicates the current fault state of the drive
(1 = FAULT, 0 = OK).
94
RESET FAULT
Command by FLN to reset a faulted drive
(1 = RESET, 0 = NO).
Parameter 1604 must be set to COMM for FLN to control this
state.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
95
MBOX PARAM
Sets the parameter to be used by the mailbox function.
96
MBOX DATA
Sets or indicates the data value of the mailbox function.
97
MBOX READ
Command by FLN to read the parameter value specified by
Point 95, MBOX PARAM. The parameter value is returned in
Point 96, MBOX DATA.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
98
MBOX WRITE
Command by FLN to write the data value specified by Point
96, MBOX DATA, to the parameter value specified by Point
95, MBOX PARAM.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
99
ERROR STATUS 1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......