ACH550-UH User’s Manual
1-231
Embedded fieldbus
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
Analog value object instance summary
The following table summarizes the Analog Value Objects supported:
AO1
AO 2
COMMAND
This object controls Analog Output 2. The
corresponding drive parameter is 0136,
COMM
VALUE
2. Control requires parameter
1507 value = 136.
Percent C
Instance
ID
Object Name
Description
Units
Present Value
Access Type
AV0
OUTPUT
SPEED
This object indicates the calculated motor
speed in RPM. The corresponding drive
parameter is 0102.
RPM
R
AV1
OUTPUT FREQ This object indicates the output
frequency applied to the motor in Hz. The
corresponding drive parameter is 0103.
Hertz
R
AV2
DC BUS VOLT
This object indicates the drive’s DC bus
voltage level. The corresponding drive
parameter is 0107.
Volts
R
AV3
OUTPUT VOLT
This object indicates the AC output
voltage applied to the motor. The
corresponding drive parameter is 0109.
Volts
R
AV4
CURRENT
This object indicates the measured
output current. The corresponding drive
parameter is 0104.
Amps
R
AV5
TORQUE
This object indicates the calculated motor
output torque as a percentage of nominal
torque. The corresponding drive
parameter is 0105.
Percent
R
AV6
POWER
This object indicates the measured
output power in kW. The corresponding
drive parameter is 0106.
Kilowatts
R
AV7
DRIVE TEMP
This object indicates the measured
heatsink temperature in °C. The
corresponding drive parameter is 0110.
°C
R
AV8
KWH (R)
This object indicates, in kW hours, the
drive’s accumulated energy usage since
the last reset. The value can be reset to
zero. The corresponding drive parameter
is 0115.
kWh
W
AV9
KWH (NR)
This object indicates the drive’s
accumulated energy usage in kW hours.
The value cannot be reset.
kWh
R
AV10
PRC PID FBCK This object is the Process PID feedback
signal. The corresponding drive
parameter is 0130.
Percent
R
Instance
ID
Object Name
Description
Units
Present Value
Access Type
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......