2-146
ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
{52} START ENA 3
This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1605 must be set to COMM for FLN to have this
control.
{53} START ENA 4
This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1606 must be set to COMM for FLN to have this
control.
{59} PAR LOCK
When switched to locked prevents parameter changes from
the panel.
1619
{68} FLN LOC CTL
Commands the bypass into FLN Local Control. In this
mode, FLN takes the bypass control from the normal
source. However, the panel’s HAND mode still has priority.
{70} DI 1 ACTUAL
This point indicates the status of bypass Digital Input 1
(1 = ON, 0 = OFF).
0103, bit 5
{71} DI 2 ACTUAL
This point indicates the status of bypass Digital Input 2
(1 = ON, 0 = OFF).
0103, bit 4
{72} DI 3 ACTUAL
This point indicates the status of bypass Digital Input 3
(1 = ON, 0 = OFF).
0103, bit 3
{73} DI 4 ACTUAL
This point indicates the status of bypass Digital Input 4
(1 = ON, 0 = OFF).
0103, bit 2
{74} DI 5 ACTUAL
This point indicates the status of bypass Digital Input 5
(1 = ON, 0 = OFF).
0103, bit 1
{75} DI 6 ACTUAL
This point indicates the status of bypass Digital Input 6
(1 = ON, 0 = OFF).
0103, bit 0
{76} RO 1 ACTUAL
This point indicates the status of bypass Relay Output 1
(1 = ON, 0 = OFF).
0104, bit 4
{77} RO 2 ACTUAL
This point indicates the status of bypass Relay Output 2
(1 = ON, 0 = OFF).
0104, bit 3
{78} RO 3 ACTUAL
This point indicates the status of bypass Relay Output 3
(1 = ON, 0 = OFF).
0104, bit 2
{79} RO 4 ACTUAL
This point indicates the status of bypass Relay Output 4
(1 = ON, 0 = OFF).
0104, bit 1
{80} RO 5 ACTUAL
This point indicates the status of bypass Relay Output 5
(1 = ON, 0 = OFF).
0104, bit 0
86
BYPASS ALARM This point indicates the current alarm state of the bypass
(1 = ALARM, 0 = OK).
88
ALARM WORD1
This point is a bit-field indicating active alarms in the
bypass.
0308
89
ALARM WORD2
This point is a bit-field indicating active alarms in the
bypass.
0309
90
LAST FAULT
This point is first in the bypass’s fault log and indicates the
most recent fault declared.
0401
93
OK.FAULT BYP
This point indicates the current fault state of the bypass
(1 = FAULT, 0 = OK).
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......