![ABB ACH550-BCR User Manual Download Page 183](http://html.mh-extra.com/html/abb/ach550-bcr/ach550-bcr_user-manual_2927183.webp)
ACH550-UH User’s Manual
1-179
Parameters
3 =
DI
3 – Enables the Interlocks function and assigns a digital input (starting with
DI
3) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFA
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0.0, and otherwise enabled).
4 =
DI
4 – Enables the Interlock function and assigns a digital input (starting with
DI
4) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFA
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0.0, and otherwise enabled).
Group 81: PFA Control
Code Description Range
Resolution
Default
S
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4…
DI
6: Free
Not allowed
1
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4: First PFA Relay
DI
5…
DI
6: Free
DI
1…
DI
2: Free
DI
3: First PFA Relay
DI
4…
DI
6: Free
2
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4: First PFA Relay
DI
5: Second PFA Relay
DI
6: Free
DI
1…
DI
2: Free
DI
3: First PFA Relay
DI
4: Second PFA Relay
DI
5…
DI
6: Free
3
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4: First PFA Relay
DI
5: Second PFA Relay
DI
6: Third PFA Relay
DI
1…
DI
2: Free
DI
3: First PFA Relay
DI
4: Second PFA Relay
DI
5: Third PFA Relay
DI
6: Free
4
Not allowed
DI
1…
DI
2: Free
DI
3: First PFA Relay
DI
4: Second PFA Relay
DI
5: Third PFA Relay
DI
6: Fourth PFA Relay
5…6
Not allowed
Not allowed
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1…
DI
3: Free
DI
4: Speed Reg Motor
DI
5…
DI
6: Free
Not allowed
1
DI
1…
DI
3: Free
DI
4: Speed Reg Motor
DI
5: First PFA Relay
DI
6: Free
DI
1…
DI
3: Free
DI
4: First PFA Relay
DI
5…
DI
6: Free
2
DI
1…
DI
3: Free
DI
4: Speed Reg Motor
DI
5: First PFA Relay
DI
6: Second PFA Relay
DI
1…
DI
3: Free
DI
4: First PFA Relay
DI
5: Second PFA Relay
DI
6: Free
3
Not allowed
DI
1…
DI
3: Free
DI
4: First PFA Relay
DI
5: Second PFA Relay
DI
6: Third PFA Relay
4…6
Not allowed
Not allowed
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......