1-82
ACH550-UH User’s Manual
Parameters
Group 01: OPERATING DATA
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Group 01: Operating Data
Code Description Range
Resolution
Default
S
0101
SPEED & DIR
-30000…30000 rpm
1 rpm
-
The calculated signed speed of the motor (rpm). The absolute value of 0101
SPEED
&
DIR
is the same as the value of
0102
SPEED
.
• The value of 0101
SPEED
&
DIR
is positive if the motor runs in the forward direction.
• The value of 0101
SPEED
&
DIR
is negative if the motor runs in the reverse direction.
0102
SPEED
0…30000 rpm
1 rpm
-
The calculated speed of the motor (rpm).
0103
OUTPUT FREQ
0.0…500.0 Hz
0.1 Hz
-
The frequency (Hz) applied to the motor.
0104
CURRENT
0.0…1.5 · I
2n
0.1 A
-
The motor current, as measured by the ACH550.
0105
TORQUE
-200.0…200.0%
0.1%
-
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque.
0106
POWER
-1.5…1.5 · P
n
0.1 kW
-
The measured motor power in kW.
0107
DC BUS VOLTAGE
0…2.5 · V
dN
1 V
-
The DC bus voltage in V DC, as measured by the ACH550.
0109
OUTPUT VOLTAGE
0…2.0 · V
dN
1 V
-
The voltage applied to the motor.
0110
DRIVE TEMP
0.0…150.0 °C
0.1 °C
-
The temperature of the drive power transistors in degrees Celsius.
0111
EXTERNAL REF 1
0.0…500.0 Hz /
0.1 Hz / 1 rpm
-
0…30000 rpm
External reference,
REF
1, in rpm or Hz – units determined by parameter 9904.
0112
EXTERNAL REF 2
0.0…100.0%
0.1%
-
(0.0…600.0% for torque)
External reference,
REF
2, in %.
0113
CTRL LOCATION
0…2
1
-
Active control location. Alternatives are:
0 =
LOCAL
1 =
EXT
1
2 =
EXT
2
0114
RUN TIME (R)
0…9999 h
1 h
-
The drive’s accumulated running time in hours (h).
• Can be
reset
by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115
KWH COUNTER (R)
0…65535 kWh
1 kWh
-
The drive’s accumulated power consumption in kilowatt hours.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be
reset
by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......