ACH550-UH User’s Manual
1-283
Diagnostics
27
CONFIG
FILE
Internal configuration file has an error. Contact your local ABB sales
representative.
28
SERIAL
1
ERR
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
).
• Communication settings (Group 51 or 53 as appropriate).
• Poor connections and/or noise on line.
29
EFB
CONFIG
FILE
Error in reading the configuration file for the embedded fieldbus.
30
FORCE
TRIP
Fault trip forced by the fieldbus. See the fieldbus User’s Manual.
31
EFB
1
Fault code reserved for the embedded fieldbus (EFB) protocol application.
These codes are not used as of the publication of this manual.
32
EFB
2
33
EFB
3
34
MOTOR
PHASE
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
35
OUTPUT
WIRING
Possible power wiring error detected. When the drive is not running it
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltageis NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
WIRING
FAULT
.
36
INCOMP
SWTYPE
The drive cannot use the software.
• Internal Fault.
• The loaded software is not compatible with the drive.
• Call support representative.
37
CB OVERTEMP
Drive control board is overheated.
Check for and correct:
• Excessive ambient temperatures
• Fan failure.
• Obstructions in the air flow.
38
USER
LOAD
CURVE
Condition defined by parameter 3701 USER LOAD C MODE has been valid
longer than the time defined by 3703 USER LOAD C TIME.
101
SERF
CORRUPT
Error internal to the drive. Contact your local ABB sales representative and
report the error number.
102
RESERVED
103
SERF
MACRO
104
RESERVED
105
RESERVED
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......