2-74
ACH550 E-Clipse Bypass User’s Manual
Parameters
Group 32: Supervisory Control
3004
COMM LOSS
1
0 = NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
NOT SEL
(0)
This parameter serves similar
purpose as parameter 3018 in
drive which specifies behavior if
Modbus link goes down.
Difference is that this parameter
applies in drive and bypass
modes and if drive node or
bypass node detects a problem.
3005
COMM TIME
0.1s
0.0 - 600.0s
10.0s
Sets the communication fault
time used with COMM LOSS
parameter.
3006
PHASE LOSS
1
0 = DISABLE
1 = ENABLE
1
Disable for input phase loss.
3007
PHASE SEQ
1
0 = DISABLE
1 = ENABLE
1
Disable for input phase
sequence fault.
3008
BYPASS MOL
1
50 - 150%
110%
Motor Overload trip level as % of
ACH550 parameter 9906
MOTOR NOM CURR.
Group 32: Supervisory Control
Code
Name
Resolution
Range
Default
Description
3201
SUPER
CTRL
1
0 = DISABLE
1 = ENABLE
DISABLE
( 0)
Enable supervisory control in
bypass mode.
3202
START LVL
1%
0 - 100%
70%
Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory
mode.
3203
STOP LEVEL
1%
0 - 100%
30%
Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory
mode.
3204
START DLY
1s
20 - 3600s
40s
Time that close condition must
be present before contactor is
closed.
Applies only in supervisory
mode.
3205
STOP DLY
1s
20 - 3600s
60s
Time that open condition must be
present before contactor is
opened.
Applies only in supervisory
mode.
3206
FBK LOSS
1
0 = BYP STOP
1 = BYP START
BYP
START
(1)
Bypass contactor operation if
drive link fault, drive AI2 loss or
excessive cycling.
Group 30: Fault Function
Code
Name
Resolution
Range
Default
Description
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......