![ABB ACH550-BCR User Manual Download Page 308](http://html.mh-extra.com/html/abb/ach550-bcr/ach550-bcr_user-manual_2927308.webp)
1-304
ACH550-UH User’s Manual
Technical data
Input power cables/wiring
Input wiring can be either:
• A four conductor cable (three phases and ground/protective earth) routed through
conduit.
• Four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drive’s load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see
Drive’s power connection terminals
on page
The table below lists copper and aluminum cable types for different load currents.
These recommendations apply only for the conditions listed at the top of the table.
IEC
NEC
Based on:
• EN 60204-1 and IEC 60364-5-2/2001
• PVC insulation
• 30 °C (86 °F) ambient temperature
• 70 °C (158 °F) surface temperature
• Cables with concentric copper shield
• Not more than nine cables laid on cable ladder
side by side.
Based on:
• NEC Table 310-16 for copper wires
• 90 °C (194 °F) wire insulation
• 40 °C (104 °F) ambient temperature
• Not more than three current-carrying
conductors in raceway or cable, or earth
(directly buried).
• Copper cables with concentric copper shield
Max
Load
Current
(A)
Cu Cable
(mm
2
)
Max
Load
Current
(A)
Al Cable
(mm
2
)
Max Load
Current
(A)
Cu Wire Size
(AWG/kcmil)
14
3x1.5
Do not use aluminum
cable with base drive
(-UH) frame sizes
R1…R4. Base drive
terminals not rated for
AI cable.
22.8
14
20
3x2.5
27.3
12
27
3x4
36.4
10
34
3x6
50.1
8
47
3x10
68.3
6
62
3x16
86.5
4
79
3x25
100
3
98
3x35
91
3x50
118
2
119
3x50
117
3x70
137
1
153
3x70
143
3x95
155
1/0
186
3x95
165
3x120
178
2/0
215
3x120
191
3x150
205
3/0
249
3x150
218
3x185
237
4/0
284
3x185
257
3x240
264
250 MCM or 2 x 1
274
3x (3x50)
291
300 MCM or 2 x 1/0
285
2x (3x95)
319
350 MCM or 2 x 2/0
345
400 MCM or 2 x 2/0
391
500 MCM or 2 x 3/0
410
2 x 3/0
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......