ACH550-UH User’s Manual
1-223
Embedded fieldbus
30
CURRENT LIM
Sets the output current limit of the drive.
2003
31
ACCEL TIME 1
Sets the acceleration time for Ramp 1.
2202
32
DECEL TIME 1
Sets the deceleration time for Ramp 1.
2203
33
HANDAUTO
ACT
Indicates whether the drive is in Hand or Auto control
(1 = HAND, 0 = AUTO).
34
ENA.DIS ACT
Indicates the status of the Run Enable command, regardless
of its source (1 = ENABLE, 0 = DISABL).
35
ENA.DIS CMD
Commanded by FLN to assert the Run Enable command
(1 = ENABLE, 0 = DISABL).
Parameter 1601 must be set to COMM for FLN to have this
control.
36
FLN LOC ACT
Indicates if the drive has been placed in “FLN LOCAL” mode
by commanding either point 68 (FLN LOC CTL) or point 69
(FLN LOC REF). Commanding either of these points to FLN
(1) “steals” control from its normal source and places in under
FLN control.
Note that the HAND mode of the panel has priority over FLN
local control.
37
FLN CTL SRC
Indicates if FLN is a source for control inputs
(1 = YES, 0 = NO).
Note that this status point is true if any of the following control
inputs are from FLN: Run/Stop, Ext1/2 Select or Run Enable.
38
FLN REF1 SRC
Indicates if FLN is the source for speed reference 1
(1 = YES, 0 = NO).
39
FLN REF2 SRC
Indicates if FLN is the source for speed reference 2
(1 = YES, 0 = NO).
40
RO1 COMMAND Controls the output state of Relay 1.
Parameter 1401 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 0
41
RO2 COMMAND Controls the output state of Relay 2.
Parameter 1402 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 1
42
RO3 COMMAND Controls the output state of Relay 3.
Parameter 1403 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 2
43
RO4 COMMAND Controls the output state of Relay 4. Access to relay 4 require
ACH550 option OREL.
Parameter 1410 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 3
44
RO5 COMMAND Controls the output state of Relay 5. Access to relay 5 require
ACH550 option OREL.
Parameter 1411 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 4
45
RO6 COMMAND Controls the output state of Relay 6. Access to relay 6 require
ACH550 option OREL.
Parameter 1412 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 5
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......