1-224
ACH550-UH User’s Manual
Embedded fieldbus
46
AO1 COMMAND Controls Analog Output 1.
Parameter 1501 must be set to this value for FLN to have this
control.
0135
(COMM
VALUE 1)
47
AO2 COMMAND Controls Analog Output 2.
Parameter 1507 must be set to this value for FLN to have this
control.
0136
(COMM
VALUE 2)
48
RESET RUN
TIME
Commanded by FLN to reset the cumulative run timer (1 =
RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
49
RESET KWH
Commanded by FLN to reset the cumulative kilowatt-hour
counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
50
PRC PID GAIN
Sets the proportional gain of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4001 (SET1)
4101 (SET2)
51
PRC PID ITIM
Sets the integration time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4002 (SET1)
4102 (SET2)
52
PRC PID DTIM
Sets the derivation time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4001 (SET1)
4101 (SET2)
53
PRC PID DFIL
Sets the time constant for the error-derivative of the active
Process PID set, as selected by Point 54, PRC PID SEL
(1 = SET2, 0 = SET1).
4004 (SET1)
4104 (SET2)
54
PRC PID SEL
Selects the active Process PID set (1 = SET2, 0 = SET1).
4027
55
EXT PID GAIN
Sets the proportional gain of the External PID controller.
4201
56
EXT PID ITIM
Sets the integration time of the External PID controller.
4202
57
EXT PID DTIM
Sets the derivation time of the External PID controller.
4203
58
EXT PID DFIL
Sets the time constant for the error-derivative of the External
PID controller.
4204
59
LOCK PANEL
Command by FLN to lock the panel and prevent parameter
changes (1 = LOCK, 0 = UNLOCK).
1602
60
INPUT REF 1
Sets Input Reference 1.
Parameter 1102 must be set to COMM for FLN to control this
value.
61
INPUT REF 2
Sets Input Reference 2.
Parameter 1106 must be set to COMM for FLN to control this
value.
62
EXT PID STPT
The setpoint for the External PID controller.
The function of this point requires parameter 4210, PID
Setpoint Select, to be set to 19 (Internal).
4211
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......