1-192
ACH550-UH User’s Manual
Embedded fieldbus
Note:
After any changes to the communication settings, protocol must be
reactivated by either cycling the drive power, or by setting parameter 5302
EFB
STATION
ID
to 0 and then restoring the station ID (5302) or use Reinitialize Device
Service.
5317
EFB PAR17
This parameter works
with parameter 5311 to
set BACnet Device
Object Instance IDs. See
parameter 5311.
Code
Description
EFB Protocol Reference
Modbus
N2
FLN
BACnet