ACH550 E-Clipse Bypass User’s Manual
2-151
Embedded fieldbus
5. Define a unique MS/TP MAC ID. Set bypass parameter 5302,
EFB
STATION
ID
=
appropriate value.
• Once this parameter is set to a non-zero value, current BACnet settings are
“latched” and used for communication until the channel is reset.
• In order to participate in MS/TP token passing, the MAC ID used must be within
the limits defined by other masters’ “Max Master” property.
6. Confirm proper BACnet communication.
• When BACnet communication is operating properly, bypass parameter 5316,
EFB PAR 16 (the MS/TP token counter), should be continually increasing.
• Bypass parameter 5306,
UART
ERRORS
, should be stable.
7. Configure the Device Object Name.
• BACnet requires a unique name for each device on the BACnet network. Write
the Object Name of the Device Object of the drive to a unique text string using the
operator workstation or software tool capable of writing BACnet properties. The
Object Name cannot be modified with the ABB display panel and only the Device
object name is writable in this product. We do not support writing of Device
Description.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......