ACH550 E-Clipse Bypass User’s Manual
2-179
Embedded fieldbus
write outside the parameter addresses, the Modbus interface returns an
exception code to the controller.
The following table summarizes the 4xxxx drive control registers 40001…40099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter
0102):
Modbus Register
Access
Remarks
4
0001
ABB
DRIVES
PROFILE
CONTROL
WORD
R/W
Maps directly to the profile’s
CONTROL
WORD
. Supported
only if bypass parameter 5305 = 0 or 2 (ABB drive
profile). Bypass parameter 5319 holds a copy in hex
format.
4
0002
Reference 1
R/W
Range = 0…+20000 (scaled to 0…1105
REF
1
MAX
), or
-20000…0 (scaled to 1105
REF
1
MAX
…0).
4
0003
Reference 2
R/W
Range = 0…+10000 (scaled to 0…1108
REF
2
MAX
), or
-10000…0 (scaled to 1108
REF
2
MAX
…0).
4
0004
ABB
DRIVES
PROFILE
STATUS
WORD
R
Maps directly to the profile‘
S
STATUS
WORD
. Supported
only if bypass parameter 5305 = 0 or 2 (ABB bypass
profile). Bypass parameter 5320 holds a copy in hex
format.
4
0005
Actual 1
(select using 5310)
R
By default, stores a copy of 0103
OUTPUT
FREQ
. Use
parameter 5310 to select a different actual value for this
register.
4
0006
Actual 2
(select using 5311)
R
By default, stores a copy of 0104
CURRENT
. Use
parameter 5311 to select a different actual value for this
register.
4
0007
Actual 3
(select using 5312)
R
By default, stores nothing. Use bypass parameter 5312
to select an actual value for this register.
4
0008
Actual 4
(select by 5313)
R
By default, stores nothing. Use bypass parameter 5313
to select an actual value for this register.
4
0009
Actual 5
(select using 5314)
R
By default, stores nothing. Use bypass parameter 5314
to select an actual value for this register.
4
0010
Actual 6
(select using 5315)
R
By default, stores nothing. Use bypass parameter 5315
to select an actual value for this register.
4
0011
Actual 7
(select using 5316)
R
By default, stores nothing. Use bypass parameter 5316
to select an actual value for this register.
4
0012
Actual 8
(select using 5317)
R
By default, stores nothing. Use bypass parameter 5317
to select an actual value for this register.
4
0031
DCU
CONTROL
WORD
LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5305 = 1. See bypass parameter 0301.
4
0032
DCU
CONTROL
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5305 = 1. See bypass parameter 0302.
4
0033
DCU
STATUS
WORD
LSW
R
Maps directly to the Least Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5305 = 1. See bypass parameter 0303.
4
0034
DCU
STATUS
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5305 = 1. See bypass parameter 0304.
40045
ACH550
REF
1 LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile’s
REF
1. Supported only if BP Parameter
5305 = 1. See drive parameter 0111.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......