1-222
ACH550-UH User’s Manual
Embedded fieldbus
10
DRIVE KWH
The drive's cumulative power consumption in kilowatt-hours.
This value may be reset by commanding FLN point 49,
RESET KWH.
0115
11
DRIVE MWH
The drive's cumulative power consumption in megawatt
hours. This value cannot be reset.
0141
12
RUN TIME
The drive's cumulative run time in hours. This value may be
reset by commanding FLN point 48, RESET RUN TIME.
0114
13
DC BUS VOLT
The DC bus voltage level of the drive.
0107
14
OUTPUT VOLT
The AC output voltage applied to the motor.
0109
15
PRC PID FBCK
The Process PID feedback signal.
0130
16
PRC PID DEV
The deviation of the Process PID output signal from its
setpoint.
0132
17
MOTOR TEMP
The measured motor temperature as set up in Group 35.
0145
18
ROTATION CNT
The motor's cumulative revolution count, in mega-
revolutions.
0142
19
N/A
20
OVRD TIME
1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
21
FWD.REV ACT
Indicates the rotational direction of the motor, regardless of
control source (1 = REV, 0 = FWD).
22
FWD.REV CMD
Commanded by FLN to change the rotational direction of the
drive.
• Parameter 1001 must be set to COMM for FLN to control
the direction of the motor by EXT1.
• Parameter 1002 must be set to COMM for FLN to control
the direction of the motor by EXT2.
23
RUN.STOP ACT
Indicates the drive's run status, regardless of control source
(1 = RUN, 0 = STOP).
24
RUN.STOP CMD Commanded by FLN to start the drive.
• Parameter 1001 must be set to COMM for FLN to control
the run state of the drive by EXT1.
• Parameter 1002 must be set to COMM for FLN to have
this control.
25
EXT1.2 ACT
Indicates whether External 1 or External 2 is the active
control source (1 = EXT2, 0 = EXT1).
26
EXT1.2 CMD
Commanded by FLN to select External 1 or External 2 as the
active control source (1 = EXT2, 0 = EXT1).
Parameter 1102 must be set to COMM for FLN to have this
control.
27
DRIVE READY
Indicates the drive is ready to accept a run command
(1 = READY, 0 = NOTRDY).
28
AT SETPOINT
Indicates the drive has reached its commanded setpoint
(1 = YES, 0 = NO)
29
DAY.NIGHT
1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......