Table 19: Programmable
Button
Description
Head Pressure Control – P
Sets the Proportional Gain of the Head Pressure Control (0.00 to 5.00; default 2.00). Use the
Change Setpoints key as described above to select/enter this setpoint. Appears when Head
Pressure Control is enabled.
Head Pressure Control – I
Sets the Integral Gain of the Head Pressure Control (0.00 to 5.00; default 2.00). Use the
Change Setpoints key as described above to select/enter this setpoint. Appears when Head
Pressure Control is enabled.
Head Pressure Control – D
Sets the Derivative Gain of the Head Pressure Control (0.00 to 5.00; default 0.00). Use the
Change Setpoints key as described above to select/enter this setpoint. Appears when Head
Pressure Control is enabled.
Table 20: Navigation
Button
Description
Home
Returns the user to Home screen.
Condenser
Returns the user to Condenser screen.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
42
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...