HYP/Mod D Variable Speed Drive screen
Figure 50: HYP/Mod D Variable Speed Drive screen
This screen displays information pertaining to a HYP/Mod D variable speed drive (VSD).
Table 77: Display only fields
Field/LED name
Description
PRV Position
Displays the pre-rotation vane position as a value between 0 and 100%.
Motor Run (LED)
Indicates whether the digital output from the controls is commanding the motor to
run.
Motor % Full Load Amps
Displays the motor current as a percentage of the Full Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit value in use. This value could come from a 0 mA to 20
mA, 0 VDC to 10 VDC, PWM signal, or SC-EQ communication interface, or a locally
programmed value.
Output Voltage
Displays the output voltage measured to the motor.
VSD Output Frequency
Displays the present output frequency to the motor.
Input Power
Displays the total kilowatts measured by the VSD or Harmonic Filter, if installed.
KW Hours
Displays the cumulative amount of kilowatts used over time as the VSD motor
controller operates.
Output Current
Phase A, B, C
Displays the phase current measured to the motor.
Voltage Total Harmonic Distortion
(L1, L2, L3) Displays the Total Harmonic Distortion (THD) for each of the voltage lines
as calculated by the filter (displayed if Harmonic Filter is present).
Supply Current Total Demand
Distortion
(L1, L2, L3) Displays the Total Dynamic Distortion (TDD) for each of the supply current
lines as calculated by the filter (displayed if Harmonic Filter is present).
Note:
For fields requiring access level of SERVICE. Service Technicians must refer to the
OptiView Control Center - Service Instructions (Form 160.76-M1)
for operation instructions and
explanation of all programmable setpoints and displayed values.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
86
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...