Table 172: Master slots numbers list for use with Trend feature
Slot
number
Description
Slot
number
Description
1792
Leaving Chilled Liquid: Temperature
2857
ACC: Surge Map Point Count
1793
Leaving Chilled Liquid: Temperature Differential
2858
ACC: Surge Map Delta P/P
1794
Leaving Chilled Liquid: Is Flow Switch Closed
2859
ACC: Surge Map Output Frequency
1795
Leaving Chilled Liquid: Is Pump On
2860
ACC: Surge Map PRV Position
1796
Leaving Chilled Liquid: Local Temperature
Setpoint
2861
Filter: Is Filter Installed
1797
Leaving Chilled Liquid: Remote Analog
Temperature Setpoint
2862
Filter: Is Operation Inhibited
1798
Leaving Chilled Liquid: Remote BAS Temperature
Setpoint
2863
Filter: Is Filter Running
1799
Leaving Chilled Liquid: Remote Modem
Temperature Setpoint
2864
Filter: Is Precharge Contactor Closed
1800
Leaving Chilled Liquid: Selected Temperature
Setpoint
2865
Filter: Is Supply Contactor Closed
1801
Leaving Chilled Liquid: Control Sensitivity
2866
Filter: Phase Rotation
1802
Leaving Chilled Liquid: Remote Temperature
Range
2867
Filter: Motor HP
1803
Leaving Chilled Liquid: Restart Temperature
Offset
2868
Filter: Supply kVA
1804
Leaving Chilled Liquid: Restart Temperature
Setpoint
2869
Filter: Total Power Factor
1805
Leaving Chilled Liquid: Shutdown Temperature
Offset
2870
Filter: DC Bus Voltage
1806
Leaving Chilled Liquid: Shutdown Temperature
Setpoint
2871
Filter: Heatsink Temperature
1807
Return Chilled Liquid: Temperature
2872
Filter: L1 - L2 RMS Voltage
1808
Evaporator: Pressure
2873
Filter: L2 - L3 RMS Voltage
1809
Evaporator: Saturation Temperature
2874
Filter: L3 - L1 RMS Voltage
1810
Evaporator: Small Temperature Difference
2875
Filter: L1 - N Peak Voltage
1811
Evaporator: Is Refrigerant Sensor Present
2876
Filter: L2 - N Peak Voltage
1812
Evaporator: Refrigerant Temperature
2877
Filter: L3 - N Peak Voltage
1813
Evaporator: Delta P / P
2878
Filter: L1 Total Harmonic Distortion
1814
Evaporator: Brine Low Cutout
2879
Filter: L2 Total Harmonic Distortion
1815
Smart Freeze Protection: Is Control Enabled
2880
Filter: L3 Total Harmonic Distortion
1816
Liquid Line Solenoid: Is Solenoid Installed
2881
Filter: L1 RMS Filter Current
1817
Liquid Line Solenoid: Is Solenoid On
2882
Filter: L2 RMS Filter Current
1818
Leaving Chilled Liquid: Remote Digital
Temperature Setpoint
2883
Filter: L3 RMS Filter Current
2048
Leaving Condenser Liquid: Temperature
2884
Filter: L1 RMS Supply Current
2049
Leaving Condenser Liquid: Is Flow Switch Closed
2885
Filter: L2 RMS Supply Current
2050
Leaving Condenser Liquid: Is Pump On
2886
Filter: L3 RMS Supply Current
2051
Return Condenser Liquid: Temperature
2887
Filter: L1 Total Demand Distortion
2052
Condenser: Pressure
2888
Filter: L2 Total Demand Distortion
2053
Condenser: Saturation Temperature
2889
Filter: L3 Total Demand Distortion
2054
Condenser: Small Temperature Difference
2890
Filter: Maximum Total Harmonic Distortion
2057
Condenser: Is High Pressure Switch Closed
2891
Filter: Maximum Total Demand Distortion
2058
Condenser: High Pressure Warning Threshold
8192
Oil: Pump Pressure
2059
SubCooling: Temperature
8193
Oil: Sump Pressure
2060
Drop Leg Refrigerant: Is Sensor Present
8194
Oil Seal Lube: Is Control Enabled
2061
Drop Leg Refrigerant: Temperature
8195
Oil Seal Lube: Time To Next Lube
2062
Vent Line Solenoid: Is Solenoid Installed
8196
Oil Seal Lube: Time Left
2063
Vent Line Solenoid: Is Solenoid On
8197
VSOP: Speed Command
2304
Motor: Starter Type
8198
VSOP: Control Mode
163
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...