programmable safety shutdown threshold. The Safety threshold in Brine applications is determined
by the Brine solution and is determined by the YORK Factory. While this condition is in effect, the
Pre-rotation Vanes are inhibited from further opening. This message automatically clears and the
Vanes are permitted to open when the Evaporator Pressure increases to the reset value.
Table 175: Threshold limits
Warning threshold (PSIG)
Reset threshold (PSIG)
Water
Brine
Water
Brine
R-513A
31.0
+1.9 more than Safety Setpoint
32.0
+3.2 more than Safety Setpoint
R-134a
27.0
+2.0 > Safety Setpoint
28.0
+3.0 > Safety Setpoint
Warning – Vanes Uncalibrated – Fixed Speed
The Compressor Motor Variable Speed Drive (VSD) is operating Fixed Speed (full speed) mode
because the Pre-rotation Vanes position potentiometer calibration has not been performed.
Warning – Harmonic Filter – Operation Inhibited
The Compressor Motor Variable Speed Drive (VSD) Harmonic Filter has been inhibited. Refer to
Variable Speed Drive – Service Instructions (Form 160.00-M1)
. Harmonic Filter operation should not be
altered by anyone other than a qualified Service Technician.
Warning – Harmonic Filter – Data Loss
Communications between the Harmonic Filter Logic Board and the Compressor Motor Variable
Speed Drive VSD Logic Board or the Adaptive Capacity Control Board is not occurring. While this
condition exists, all filter related parameters are displayed as X’s. This message automatically clears
when communications are restored.
Warning – Harmonic Filter – Input Frequency Range
The power line frequency detected by the Compressor Motor Variable Speed Drive (VSD) Harmonic
Filter is outside the range of 58 to 62 Hz (60 Hz), or 49 to 51 Hz (50 Hz). While this condition exists,
all filter related parameters are displayed as X’s. This message automatically clears when the line
frequency is within range.
Warning – Harmonic Filter – Not Running
This warning is set when all of the following are true for 20 continuous seconds:
•
Chiller is running
•
Filter is enabled
•
Filter present status is true
•
Run Time greater than 20 seconds
•
Filter operating mode is stopped
This warning is released when the chiller is stopped, but will be displayed until manually cleared
using the WARNING RESET key when logged in at OPERATOR (or higher) access level.
Warning – Vanes Uncalibrated
The Hot Gas Bypass feature is enabled, but the Pre-rotation Vanes calibration procedure has not yet
been performed.
Warning – External I/O – Serial Communications
Serial communications between the Microboard and the optional Analog I/O Board has been
interrupted for at least 20 seconds.
169
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...