Table 108: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Winding Setup Service
JCI Service
Not shown when Winding Temperature Protection Setpoint on Motor
Details screen is set to Disabled. Allows a Service Technician to program
the High Winding Temperature (266°F to 320°F; default 311°F) and
Winding Hotspot Allowance (0°F to 18°F; default 0°F) safety shutdown
thresholds. Values entered are displayed in the respective data boxes.
Vibration Gain Admin
Admin
Only shown when access level is Admin and Motor Vibration Protection
Setpoint on Motor Details screen is not set to Disabled. Allows a Service
Technician to enter values for vibration Input Gain (1:1, 11:1, 21:1
[default]).
Bearing Setup Service
JCI Service
Not shown when Bearing Temperature Protection Setpoint on Motor
Details screen is set to Disabled. Allows a Service Technician to enter
values for High Bearing Temperature Shutdown (149°F to 212°F; default
203°F) and Warning (140°F to 194°F; default 194°F) thresholds.
Temperature
Disable
Admin
Admin
Only shown when access level is Admin and Winding Temperature
Protection Setpoint on Motor Details screen is not set to Disabled. Allows
a Service Technician to disable individual winding temperature sensors.
The respective temperature data box reflects enabled or disabled status.
This could be applied to defective sensors or for service reasons. When a
sensor is disabled, the respective temperature data box does not appear
on the Motor Details screen.
Table 109: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home
Service
JCI Service
Returns the user to Home screen.
Motor Details
Service
JCI Service
Returns the user to Motor Details screen.
113
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...