Table 99: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Motor Lube
Date
Admin
Admin
Allows modification of the Date of Last Motor Lubrication.
Start Auto Lube Service
JCI Service
This button is only displayed when automatic lubrication hardware is
installed and the setpoint is set in the Setup Screen. When the Auto-
Lube is enabled, no lubrication warnings or safety shutdowns will occur.
Pressing this button starts the auto-lube procedure for the P203 lube
system.
Motor Lube
Acknowledge
Operator
Standard
When the motor lubrication has been performed, the Operator must
acknowledge the lubrication has been performed. This is done by
entering his/her initials, name or user ID as a 3 to 8 character string. The
entry is displayed as the Operator Initials at Last Lubrication. The date
and time of this entry is automatically logged as the Date of Last Motor
Lubrication and Time of Last Motor Lubrication. This entry also resets the
operating hours since last lubrication to zero.
This entry also resets the motor lubrication warning messages
WARNING
– MOTOR BEARING LUBE SUGGESTED
,
WARNING – MOTOR BEARING
LUBE REQUIRED
, and the safety shutdown message
Motor – Lack Of
Bearing Lubrication
.
Enter your initials, name or user ID using the following procedure. The
entry must be a minimum of 3 characters and a maximum of 8 characters.
•
At the keypad, log in at Operator access level using password 9 6
7 5. If resetting the safety shutdown Motor – Lack Of Lubrication,
place Compressor Switch in Stop-Reset (O) position.
•
Press the Motor Lube Acknowledge key on the Motor Lubrication
Screen. A dialog box appears. A red box highlights the first
changeable location.
•
Use the ▲▼ keys to scroll sequentially through the alphabet to
enter letters or numbers. Each time the ▲ is pressed, the next
higher sequential alphabet letter or number is displayed. Each
time the ▼ is pressed, the next lower alphabet letter or number is
displayed. When the desired letter or number is displayed, use the
► key to forward space the red box for the next entry. Use the ◄
key to backspace, if necessary. To write over an existing entry or
to place a blank space, scroll to the beginning of the alphabet. The
selection prior to the letter A is a blank space. Use the ● key to enter
a period/decimal point. During the entry process, if it is desired to
exit the dialog box and retain the previous entry, press the Cancel
(X) key.
•
When all of the required characters have been entered, press the
Enter key.
Table 100: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home
View
View
Returns the user to Home screen.
Motor
View
View
Returns the user to Motor screen.
103
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...